TABLE II. Capacities for R-22 (Btuh) -Continued 11 21 31 41
MS PIN |
57.2°C condensing temp, 51.7°C vapor free liquid entering thermostatic expansion valve (TEV) |
40.6°C conditioning temperature 29.4°C vapor free liquid entering TEV |
||||||||||
-23.3°C evaporator (EVAP) temperature 17.2 bar pressure drop (PD) |
-3.9°F EVAP temperature 15.2 bar PD |
-23.3°C EVAP temperature 15.2 bar PD |
-3.9°C EVAP temperature 13.8 bar PD |
10.0°C EVAP temperature 12.1 bar PD |
10.0°C EVAP temperature 5.2 bar PD |
|||||||
MS17982 |
Min |
Max |
Min |
Max |
Min |
Max |
Min |
Max |
Min |
Max |
Min |
Max |
-13 |
224.1 |
346.1 |
367.5 |
1129.4 |
||||||||
-14 |
403.3 |
608.8 |
706.7 |
986.0 |
||||||||
-15 |
520.6 |
1006.6 |
989.4 |
1723.7 |
||||||||
-16 |
982.5 |
2220.1 |
2068.4 |
3433.6 |
||||||||
-17 |
1503.1 |
3240.5 |
2757.9 |
4929.8 |
||||||||
-18 |
1530.6 |
2116.7 |
12962.1 |
1689.2 |
||||||||
-19 |
3288.8 |
3999.0 |
2675.2 |
2861.3 |
||||||||
-20 |
4688.4 |
6101.9 |
3771.4 |
4550.5 |
||||||||
-21 |
6687.9 |
8825.3 |
4688.4 |
7032.7 |
||||||||
-22 |
8446.1 |
9170.0 |
6377.7 |
7032.7 |
||||||||
-23 |
12803.6 |
15306.4 |
9239.0 |
10342.1 |
||||||||
-24 |
16685.3 |
20201.6 |
13017.3 |
15237.4 |
11 Minimum capacity requirements must be met.
21 Maximum capacities are merely for the application engineer.
31 The suffix "A" in tables III and IV does not affect capacity.
41 Metric equivalents are given for information only.