MIL-PRF-12125H
a. Apply a hydrostatic pressure of not less than 350 psi (2410 kPa) at 150±5 °F
(65 ±3 °C) to the valve with both ends blanked and the gate in the open position.
b. Relieve the pressure, close the gate and apply a hydrostatic pressure of not less than
200 psi (1380 kPa) at 150 ±5 °F (65 ±3ºC) to one side of the valve with the other side
open to the atmosphere.
c. Open the valve approximately halfway and lock the lever mechanism.
d. Unlock the lever mechanism and rapidly open and close the valve 10 times.
e. Relieve the pressure, disconnect the pressure line and attach it to the other side of the
valve.
f. Apply a hydrostatic pressure of not less than 200 psi (1380 kPa) at
150 ±5ºF (65 ±3ºC) to one side of the valve with the other side open to the
atmosphere. Nonconformance to 3.4 shall constitute failure of this test.
5. PACKAGING
5.1 Packaging. For acquisition purposes, the packaging requirements shall be as
specified in the contract or order (see 6.2). When actual packaging of materiel is to be
performed by DoD personnel, these personnel need to contact the responsible packaging activity
to ascertain requisite packaging requirements. Packaging requirements are maintained by the
Inventory Control Point s packaging activity within the Military Department or Defense Agency,
or within the Military Department s System Command. Packaging data retrieval is available
from the managing Military Department s or Defense Agency s automated packaging files, CD-
ROM products, or by contacting the responsible packaging activity.
6. NOTES
(This section contains information of a general or explanatory nature which may be helpful, but
is not mandatory.)
6.1 Intended use. The valves are intended for use principally in water purification
equipment.
6.2 Acquisition requirements. Acquisition documents should specify the following:
a.
Title, number, and date of the specification.
b.
Style and size required (see 1.2).
c.
If required, the specific issue of individual documents referenced (see 2.2).
d.
When a first article is required for inspection and approval, and number of valves
required (see 3.1).
e.
Color required (see 3.8).
f.
When identification marking other than specified is required (see 3.9).
g.
Packaging requirements (see 5.1).
h.
Specification part number required (see 1.3).
9